Fire Sprinkler Inspection, Testing & Repair | Hedrick Fire Protection
Fire sprinkler system serviced by Hedrick Fire Protection

Fire Sprinklers

At Hedrick Fire Protection, we are your one-stop shop for everything related to fire protection and safety, including fire sprinkler services. Our mission is to provide top-notch fire protection services that keep your buildings and properties safe and secure. With over 150 years of combined experience, our team delivers the highest standard of customer service and expertise in fire protection systems throughout California.

The Importance of Functional Fire Sprinkler Systems

Fire sprinkler systems are not just a regulatory requirement; they are a crucial element in safeguarding lives and assets. A sprinkler system spends years doing nothing visible, then has to perform perfectly the instant a fire starts. Inadequate or malfunctioning fire protection can lead to devastating consequences, including loss of life, property damage, and financial setbacks. The most common reason a system fails in a real fire is simple: a control valve was left closed. That is exactly why regular inspection and testing matter, and why business owners and facility managers need a fire sprinkler contractor they can trust.

Comprehensive Fire Sprinkler Services

As a leading fire sprinkler company in Los Angeles, Hedrick Fire Protection offers a complete range of sprinkler system services to meet your specific needs. Select a service below to see what it includes.

NFPA 25 requires a deeper round of inspection and testing every five years. This scope includes an internal examination of the piping to check for corrosion, scale, and obstructions, testing or replacement of system pressure gauges, internal inspection of the water-flow control valves, full backflow preventer testing, and standpipe hydrostatic testing where those systems are present. We complete the full five-year scope, document the results, and provide the certification your Authority Having Jurisdiction (AHJ) and insurer expect.

Once a year we perform the comprehensive NFPA 25 inspection and functional test. That includes a visual check of every accessible sprinkler head for corrosion, paint, or damage, a main drain test at the riser to confirm the water supply, testing of control valves and alarm devices, a trip test on any dry-pipe or deluge valves, and verification that the fire department connection is clear and labeled. You receive full documentation of any deficiencies found and the corrective steps needed.

Every three months we test and inspect the components that need closer attention: water-flow alarm devices, supervisory and valve tamper signal devices, control valves, hydraulic nameplates, and the fire department connection. Quarterly checks are designed to catch a closed valve or a silent alarm long before it becomes a problem in an emergency.

From new system installation designed to NFPA 13, to repairs and individual head replacements, our licensed technicians handle the full range of work. Any sprinkler showing corrosion, paint, loading, or physical damage is replaced rather than cleaned, and we correct any deficiencies found during inspection so the system stays compliant and ready to perform.

When a space is reconfigured, walls move and ceilings change, and sprinkler coverage has to change with them. We modify, relocate, add, or cap sprinkler heads so coverage matches the new floor plan and meets code, coordinating with your build-out schedule and the local AHJ to keep the project on track.

The NFPA 25 Inspection Schedule

Fire sprinkler systems are not inspected on a single annual visit. NFPA 25 sets layered intervals, with the most critical and easy-to-check components looked at most often. Here is how the cadence breaks down:

NFPA 25 Fire Sprinkler Inspection Cadence WEEKLY Control valves and gauges on dry, preaction, and deluge systems MONTHLY Gauges and valves on wet pipe systems; valve supervision QUARTERLY Water flow alarms, tamper and supervisory devices, FDC, main drain test ANNUAL Full system inspection, head check, valve and alarm testing EVERY 5 YEARS Internal pipe inspection, gauge testing, backflow and standpipe testing

Intervals shown are typical NFPA 25 requirements. The exact schedule depends on your system type (wet pipe, dry pipe, preaction, or deluge). Trained in-house staff may perform the weekly and monthly checks, while the quarterly, annual, and five-year work and all functional testing should be performed by a licensed fire protection contractor.

Why Choose Hedrick Fire Protection?

Hedrick Fire Protection has an unwavering commitment to excellence and customer satisfaction. Our knowledgeable staff brings decades of experience to the table, ensuring that every project is executed flawlessly from start to finish. We handle the full lifecycle of your system, from installation and tenant improvements to the recurring inspections that keep it compliant, so you have one trusted contractor for everything.

So, what are you waiting for?

Frequently Asked Questions

NFPA 25 sets layered intervals. Quick visual checks of valves and gauges are done weekly or monthly, a more detailed round of testing is done quarterly, a full inspection and functional test is done annually, and a deeper internal inspection happens every five years. The exact schedule depends on your system type.

It is the every-five-year scope required by NFPA 25. It includes an internal inspection of the piping for corrosion and obstructions, testing or replacement of pressure gauges, internal inspection of control valves, and backflow and standpipe testing where those systems apply. We document the results for your compliance records.

Yes. Any head showing corrosion, paint, loading, or physical damage is replaced rather than cleaned. NFPA 25 also requires sample testing of heads based on type and age. As a general guide, standard sprinklers are sampled around 50 years, fast-response heads around 20 to 25 years, and harsh or high-temperature heads more often, with replacement of the group if a sample fails.

Trained in-house staff can perform the routine weekly and monthly visual checks. The quarterly, annual, and five-year inspections, and all functional testing, should be performed by a licensed fire protection contractor.

It is a test performed at the system riser that opens the main drain and compares the static pressure to the flowing pressure. A significant drop can indicate an obstruction or a partially closed valve in the water supply. It is part of the annual inspection.

Yes. We design and install new systems to NFPA 13, and we modify, relocate, add, or cap heads during tenant improvements so coverage matches the new layout and meets code.